五月天手机无码av_色色图片区_97人人人人人人了_玖玖无码,免费无码片岛国在线看,A级毛片成年毛片20以上无码毛片,欧美成手机版在线视频,欧美一区高清,爱爱精品,成年轻人电影无码,h视频在线免费看

川消_萃聯(lián)
氣體滅火系統(tǒng)
自動(dòng)噴水滅火系統(tǒng)

聯(lián)系我們

  • 萃聯(lián)(山東)消防設(shè)備有限責(zé)任公司
  • 電話:15508683119
  • 地址:山東省濟(jì)南市歷城區(qū)祝舜路44號(hào)
當(dāng)前位置:首頁(yè) > 新聞中心消防水泵控制閥的使用保養(yǎng)要注意什么,!

消防水泵控制閥的使用保養(yǎng)要注意什么!

來源:http://n3462.cn/ 日期:2022-03-04

1,、每日檢查消防水泵控制閥保養(yǎng)部分,,要求控制部分完好;泵組密封情況,消防水泵控制閥投入運(yùn)行前每秒滴水不超過一滴,。
1. Check the maintenance part of the control valve of the fire pump every day, and the control part is required to be intact; The sealing condition of the pump set, and the water drop per second shall not exceed one drop before the control valve of the fire pump is put into operation.
保養(yǎng)內(nèi)容:
Maintenance contents:
1,、每周消防水泵控制閥保養(yǎng)起碼運(yùn)行一次,運(yùn)行時(shí)間電動(dòng)泵不少于10min,、柴油泵啟動(dòng)不少于30min,,檢查水泵出水壓力是否符合要求。
1. The control valve of the fire pump shall be maintained and operated at least once a week. The operation time of the electric pump shall not be less than 10min and that of the diesel pump shall not be less than 30min. Check whether the outlet pressure of the water pump meets the requirements.
2、每周消防水泵控制閥運(yùn)行前,,檢查泵組是否完好,。好比說,泵的吸水,、出手,、旁通管能全部開放;泵組無泄漏;進(jìn)、出管壓力表正常;消防水池儲(chǔ)滿消防用水細(xì)節(jié)問題,。
2. Check whether the pump set is in good condition every week before the operation of the fire pump control valve. For example, the suction, hand and bypass pipes of the pump can be fully opened; The pump set has no leakage; Inlet and outlet pressure gauges are normal; Details of fire water tank full of fire water.
川消
3,、消防水泵控制閥運(yùn)行前,檢查電器控制部分是否完好,。好比說電源開關(guān)指示正指示燈正常;切換,、轉(zhuǎn)換指示燈正常;備電啟動(dòng)、隔離開關(guān)關(guān)閉;報(bào)警反饋信號(hào)指示燈不亮,、正常指示燈開啟等細(xì)節(jié)問題,。
3. Before the fire pump control valve is operated, check whether the electrical control part is intact. For example, the positive indicator light of the power switch is normal; Switching and switching indicators are normal; Standby power start and disconnector close; The alarm feedback signal indicator is not on, and the normal indicator is on.
4、檢查主,、備電源切換正常,,檢查備用電源,看能否確保在30s內(nèi)使水泵投入正常運(yùn)行;檢測(cè)備用水泵能否自動(dòng)切換投入運(yùn)行,。
4. Check whether the switching between main and standby power supply is normal and whether the standby power supply can ensure the normal operation of the water pump within 30s; Check whether the standby water pump can be automatically switched and put into operation.
保養(yǎng)工作:
Maintenance work:
1,、定期檢查消防水泵控制閥保養(yǎng)出水管路上閘閥、止回閥,、水錘裝置是否正常,。
1. Regularly check whether the gate valve, check valve and water hammer elimination device on the outlet pipe of the fire pump control valve maintenance are normal.
2、定期吸水管入口處雜物,,防止堵塞,。如若消防泵所處環(huán)境衛(wèi)生條件優(yōu)良,可2-3月檢查一次雜物,。
2. Regularly remove sundries at the inlet of the suction pipe to prevent blockage. If the environmental sanitation condition of the fire pump is good, the sundries can be checked once in February to March.
3,、打開末端試水裝置或消火栓放水,檢查消防水泵控制閥能否正常啟動(dòng),,以此確保消防泵使用時(shí)水泵能正常工作,。
3. Open the end water test device or fire hydrant to discharge water, and check whether the control valve of the fire pump can be started normally, so as to ensure that the water pump can work normally when the fire pump is used.
在消防水泵控制閥運(yùn)行前,應(yīng)由操作人員進(jìn)行監(jiān)督,,以免發(fā)生事故,。
Before the operation of the fire pump control valve, the operator shall supervise it to avoid accidents.
長(zhǎng)期運(yùn)行后,由于機(jī)械磨損,,設(shè)備的噪音和振動(dòng)會(huì)增加,。應(yīng)該停止并檢查它。有必要更換易損部件和軸承。該泵的大修周期通常為一年,。
After long-term operation, the noise and vibration of the equipment will increase due to mechanical wear. It should be stopped and checked. It is necessary to replace vulnerable parts and bearings. The overhaul cycle of the pump is usually one year.
川消專注行業(yè)多年,用心服務(wù)客戶,您的滿意就是我們的發(fā)展,詳情點(diǎn)擊:http://n3462.cn
Sichuan consumer has focused on the industry for many years and served customers wholeheartedly. Your satisfaction is our development. For details, click: http://n3462.cn
上一篇:煙感報(bào)警器的工作原理是什么,?
下一篇:超細(xì)干粉滅火裝置的適用性能!

相關(guān)產(chǎn)品 / Related products