電控消防水炮安裝運(yùn)輸不合格的后果
來源:http://n3462.cn/ 日期:2023-04-17
電控消防水炮為電動(dòng)有線和無線遙控兩種直流驅(qū)動(dòng)控制方式,,實(shí)現(xiàn)操作人員能夠在遠(yuǎn)距離直接控制消防炮射水角度,能很好的保護(hù)滅火人員的人身,。下面
川消小編來講講電控消防水炮安裝運(yùn)輸不合格的后果吧,。
The electric fire water monitor adopts two DC drive control methods: electric wired and wireless remote control, which enables operators to directly control the water injection angle of the fire monitor from a long distance, effectively protecting the personal safety of firefighters. Next, let's talk about the consequences of unqualified installation and transportation of electronic fire water monitors.
1、若不沖洗,,則不僅會(huì)使電動(dòng)閥關(guān)閉不嚴(yán),,還會(huì)使雜物堵塞水炮炮嘴,進(jìn)而影響水炮射程和流量,。
1. If not flushed, not only will the electric valve not be tightly closed, but it will also cause debris to block the nozzle of the water cannon, thereby affecting the range and flow rate of the water cannon.
2,、若與其他系統(tǒng)共用一個(gè)泵房系統(tǒng),則水炮管網(wǎng)壓力達(dá)不到額定工作壓力
2. If sharing a pump room system with other systems, the pressure of the water cannon pipeline network cannot reach the rated working pressure
3,、若不裝,,則管道內(nèi)有雜質(zhì)會(huì)使電動(dòng)閥關(guān)閉不嚴(yán),進(jìn)而出現(xiàn)長(zhǎng)期漏滴水現(xiàn)象以及會(huì)堵住炮口,。這會(huì)造成后期維護(hù)難度很大,。
3. If not installed, impurities in the pipeline will cause the electric valve to close loosely, leading to long-term water leakage and blockage of the gun mouth. This will make maintenance difficult in the later stage.
4、若裝反,,則會(huì)造成電動(dòng)閥開關(guān)相反,,調(diào)試水炮時(shí)現(xiàn)場(chǎng)控制箱顯示關(guān)閥,實(shí)際是開閥,,造成誤噴水,。
4. If installed in the wrong direction, it will cause the electric valve to switch in the opposite direction. When debugging the water cannon, the on-site control box shows that the valve is closed, but in reality, it is open, causing incorrect water spraying.
5、若安裝距離過近,,電動(dòng)閥轉(zhuǎn)動(dòng)時(shí),,擋板會(huì)被法蘭卡住導(dǎo)致關(guān)閉不嚴(yán)、電動(dòng)閥燒壞,,以及射水流量不夠
5. If the installation distance is too close, the baffle will be stuck by the flange when the electric valve rotates, resulting in loose closure, burnt electric valve, and insufficient water injection flow rate

6,、若太高,則不方便現(xiàn)場(chǎng)施工和日后檢修維護(hù)。
6. If it is too high, it will be inconvenient for on-site construction and future maintenance.
7,、20-80L/S為DN100;100-120L/S為DN150;150-200L/S為DN200;其他流量請(qǐng)聯(lián)系廠家,,若小于該標(biāo)準(zhǔn),則不符合消防驗(yàn)收標(biāo)準(zhǔn),。
7. 20-80L/S is DN100; 100-120L/S is DN150; 150-200L/S is DN200; For other flow rates, please contact the manufacturer. If it is less than this standard, it does not meet the fire acceptance standards.
8,、20-80L/S為DN100;100-120L/S為DN150;150-200L/S為DN200;其他流量請(qǐng)聯(lián)系廠家會(huì)造成水炮轉(zhuǎn)動(dòng)或噴水顫動(dòng)避免造成法蘭之間漏水,損壞水炮電子元件
8. 20-80L/S is DN100; 100-120L/S is DN150; 150-200L/S is DN200; For other flow rates, please contact the manufacturer to avoid water leakage between flanges and damage to the electronic components of the water cannon, which may cause rotation or water jet vibration
9,、水炮控制箱控制系統(tǒng)為電路板時(shí),,須在安裝水炮控制箱前將地址碼設(shè)定好,撥碼方式:1號(hào)炮撥1,,2號(hào)炮撥2,,3號(hào)炮撥1、2,,4號(hào)炮撥3,,以此類推,控制箱撥碼為二進(jìn)制,。否則將會(huì)影響后期水炮調(diào)試增加不必要的麻煩,。
9. When the control system of the water cannon control box is a circuit board, the address code must be set before installing the water cannon control box. The dialing method is: 1 for gun 1, 2 for gun 2, 1, 2 for gun 3, 3 for gun 4, and so on. The dialing code of the control box is binary. Otherwise, it will affect the later water cannon debugging and increase unnecessary trouble.
10、水炮控制箱控制系統(tǒng)為繼電器時(shí),,則無需編碼,。會(huì)影響水炮的正常旋轉(zhuǎn)
10. When the control system of the water cannon control box is a relay, there is no need for coding. It will affect the normal rotation of the water cannon
11、若距吊頂太近,,則炮嘴仰起噴水會(huì)打到頂棚上,。
11. If it is too close to the suspended ceiling, the nozzle will lift up and spray water onto the ceiling.
12、若不是,,則容易造成通訊故障(RS485故障),;視頻模糊,。
12. If not, it is easy to cause communication failure (RS485 failure); Video blurring.
電控消防水炮安裝運(yùn)輸不合格的后果相關(guān)內(nèi)容就講解到這里了,,您對(duì)此有怎樣的疑惑或者需求可以隨時(shí)來我們網(wǎng)站
http://n3462.cn進(jìn)行咨詢了解!
That's all for the consequences of unqualified installation and transportation of electronic fire water monitors. If you have any doubts or needs, please feel free to visit our website at any time http://n3462.cn Conduct consultation to understand!