室外消火栓的距離不應(yīng)超過多少米
來源:http://n3462.cn/ 日期:2023-06-06
室外消火栓設(shè)置安裝應(yīng)明顯容易發(fā)現(xiàn),方便出水操作,地下消火栓還應(yīng)當在地面附近設(shè)有明顯固定的標志,。地上式消火栓選用于氣候溫暖地面安裝,地下室選用于氣候寒冷地面安裝,。那你知道室外消火栓的距離不應(yīng)超過多少米嗎?下面
川消小編為您分析:
The installation of outdoor fire hydrants should be clearly visible and easy to detect, making it convenient for water outlet operations. Underground fire hydrants should also have clear and fixed signs near the ground. The above ground fire hydrant is selected for installation on warm climates, and the basement is selected for installation on cold climates. Do you know how many meters should the distance between outdoor fire hydrants not exceed? Below, the editor of Chuanxiao will analyze for you:
1,、當建筑物在市政消火栓保護半徑150m以內(nèi),,且消防用水量不超過15L/s時,可不設(shè)室外消火栓,。
1. When the building is within a radius of 150m of municipal fire hydrant protection and the fire water consumption does not exceed 15L/s, outdoor fire hydrants may not be installed.
2,、室外消火栓應(yīng)沿高層建筑周圍均勻布置,并不宜集中在建筑物一側(cè)。
2. Outdoor fire hydrants should be evenly arranged around high-rise buildings and should not be concentrated on one side of the building.
3,、人防工程室外消防栓距人防工程入口不宜小于5m,。
3. The distance between the outdoor fire hydrant of the civil air defense project and the entrance of the civil air defense project should not be less than 5m.
4、停車場的室外消防栓宜沿停車場周邊設(shè)置,,且距離近一排汽車不宜小于7m,距加油站或庫不宜小于15m,。
4. The outdoor fire hydrants in the parking lot should be set along the perimeter of the parking lot, and should not be less than 7m from the nearest row of cars, and should not be less than 15m from the gas station or garage.
5、室外消防栓應(yīng)設(shè)置在便于消防車使用的地點,。
5. Outdoor fire hydrants should be located in locations that are convenient for fire trucks to use.
6,、室外消防栓宜采用地上式,當采用地下式消火栓時,,應(yīng)有明顯標志,。寒冷地區(qū)采用地下式,非寒冷地區(qū)宜采用地上式,,地上式有條件可采用防撞型,。
6. Outdoor fire hydrants should be of the above ground type, and when underground fire hydrants are used, there should be clear signs. Underground type is used in cold areas, while above ground type is recommended in non cold areas. If conditions permit, anti-collision type can be used for above ground type.
7、室外地上式消防栓應(yīng)有一個直徑為150mm或100mm和兩個直徑為65mm的栓口,。室外地下式消火栓應(yīng)有直徑為100和65mm的栓口各一個,。
7. Outdoor aboveground fire hydrants should have one diameter of 150mm or 100mm and two diameter of 65mm. Outdoor underground fire hydrants should have one hydrant mouth with a diameter of 100 and one hydrant mouth with a diameter of 65mm.
8、室外消防栓的保護半徑不應(yīng)超過150m,間距不應(yīng)超過120m,。
8. The protection radius of outdoor fire hydrants should not exceed 150m, and the spacing should not exceed 120m.
9,、室外消防栓距路邊不應(yīng)超過2m,距房屋外墻不宜小于5m。
9. The outdoor fire hydrant should not exceed 2m from the roadside and should not be less than 5m from the exterior wall of the house.
針對室外消火栓的距離不應(yīng)超過多少米這個問題,,以上內(nèi)容為您做了解答,,希望能夠給您好的幫助,,更多事項就來我們網(wǎng)站
http://n3462.cn咨詢!
Regarding the question of how many meters should the distance between outdoor fire hydrants not exceed, the above content has provided an answer for you. We hope it can provide you with good help. For more information, please come to our website http://n3462.cn consulting service