細水霧滅火泵組常見故障分析與處理
來源:http://n3462.cn/ 日期:2023-06-29
1、泵組連接處有滲漏
1. Leakage at the connection of the pump unit
(1)故障原因分析:連接件松動;連接處O 型圈或密封墊損壞,;連接件損壞,。
(1) Fault cause analysis: loose connectors; Damaged O-ring or sealing gasket at the connection; Damaged connectors.
(2)故障處理:擰緊連接件;更換O型圈或密封墊,;更換連接件,。
(2) Fault handling: Tighten the connectors; Replace the O-ring or sealing gasket; Replace the connector.
2、泵組出口壓力低
2. Low outlet pressure of pump unit
(1)故障原因分析:泵組測試閥未關(guān)閉,;泵組進線電源反相,;高壓泵損壞;使用流量超出額定值,。
(1) Fault cause analysis: The testing valve of the pump unit was not closed; The power supply of the pump unit inlet is in reverse phase; High pressure pump damaged; The usage flow exceeds the rated value.
(2)故障處理:關(guān)閉泵組測試閥,;調(diào)整進線電源相序;更換高壓泵,;在泵組額定值內(nèi)工作,。
(2) Fault handling: Close the pump unit test valve; Adjust the phase sequence of the incoming power supply; Replace the high-pressure pump; Working within the rated value of the pump set.
3. Chuanxiao pump group does not start
(1)故障原因分析:高壓泵接觸器未閉合,;泵組停止觸點斷開,;LOGO!未執(zhí)行程序,;電源未接通,;斷水水位保護。
(1) Fault cause analysis: The high-pressure pump contactor is not closed; The pump unit stop contact is disconnected; LOGO! Not executing the program; The power supply is not connected; Water cut-off level protection.
(2)故障處理:閉合接觸器,;閉合泵組停止觸點,;檢修LOGO!必要時更換,;接通電源,;恢復調(diào)節(jié)水箱水位。
(2) Fault handling: Close the contactor; Close the pump unit stop contact; Repair the logo! Replace if necessary; Connect the power supply; Restore the water level of the regulating water tank.
4,、穩(wěn)壓泵頻繁啟動
4. Frequent start-up of pressure stabilizing pump
(1)故障原因分析:管道有滲漏,;泄壓閥密封不好;測試閥未關(guān)緊,;單向閥密封墊上粘連雜質(zhì),。
(1) Fault cause analysis: There is leakage in the pipeline; Poor sealing of safety relief valve; The test valve is not tightly closed; Adhesive impurities on the sealing gasket of the one-way valve.
(2)故障處理:管道滲漏點補漏;檢修泄壓閥,;完全關(guān)閉測試閥,;清洗單向閥并清潔水箱及管道。
(2) Fault handling: repairing pipeline leakage points; Maintain the safety relief valve; Fully close the test valve; Clean the one-way valve and clean the water tank and pipelines.
5,、穩(wěn)壓泵規(guī)定時間內(nèi)不能恢復壓力
5. The regulated pump cannot restore pressure within the specified time
(1)故障原因分析:管道內(nèi)殘存空氣,;管道有滲漏,;高壓球閥滲漏;穩(wěn)壓泵出口壓力低,;穩(wěn)壓泵損壞,。
(1) Fault cause analysis: residual air in the pipeline; There is leakage in the pipeline; Leakage of high-pressure ball valve; Low outlet pressure of the pressure stabilizing pump; The pressure stabilizing pump is damaged.
(2)故障處理:完全排除管道空氣;管道滲漏點補漏,;見下文高壓球閥滲漏故障處理方法,;調(diào)節(jié)穩(wěn)壓泵壓力調(diào)節(jié)螺絲;更換穩(wěn)壓泵,。
(2) Fault handling: completely eliminate the air in the pipeline; Pipeline leakage point repair; Refer to the following methods for handling leakage faults of high-pressure ball valves; Adjust the pressure regulating screw of the stabilizing pump; Replace the pressure stabilizing pump.
細水霧滅火泵組常見故障分析與處理相關(guān)事項就講解到這里了,,希望能夠給您好的幫助,更多事項就來我們網(wǎng)站
http://n3462.cn咨詢,!
That's all for the analysis and handling of common faults in the water mist fire extinguishing pump group. We hope to provide you with good help. For more information, please visit our website http://n3462.cn consulting service