預(yù)作用報(bào)警閥是將火災(zāi)探測(cè)報(bào)警技術(shù)和自動(dòng)噴水系統(tǒng)結(jié)合起來(lái),,對(duì)保護(hù)對(duì)象起雙重保護(hù)作用的自動(dòng)噴水滅火裝置。具有干式系統(tǒng)的特點(diǎn),。預(yù)作用報(bào)警閥通常安裝于那些既需要用水滅火,,但又不允許發(fā)生非火災(zāi)原因而噴水的地方。適用于貯藏真本的圖書館、檔案室,、博物館,、貴重物品貯藏室、電腦機(jī)房等,。下面
川消小編為您講解更多:
The pre action alarm valve is an automatic sprinkler system that combines fire detection and alarm technology with an automatic sprinkler system to provide dual protection for the protected object. It has the characteristics of a dry system. Pre action alarm valves are usually installed in places that require water to extinguish fires, but do not allow water to be sprayed for non fire reasons. Suitable for storing rare and authentic books in libraries, archives, museums, storage rooms for valuable items, computer rooms, etc. Below, the editor of Chuanxiao will explain more to you:
預(yù)作用系統(tǒng)的預(yù)作用報(bào)警閥是由雨淋閥和濕式報(bào)警閥上下串接而成,,雨淋閥位于供水側(cè),濕式報(bào)警閥位于系統(tǒng)側(cè)而成為預(yù)作用閥組,。系統(tǒng)由預(yù)作用閥水力警鈴,、壓力開關(guān)、空壓機(jī),、空氣維護(hù)裝置,、信號(hào)碟閥等組成,安裝閉式灑水噴頭,,并以常用的探測(cè)系統(tǒng)作為報(bào)警和啟動(dòng)的裝置,。
The pre action alarm valve of the pre action system is composed of a deluge valve and a wet alarm valve connected in series. The deluge valve is located on the water supply side, and the wet alarm valve is located on the system side, forming the pre action valve group. The system consists of a pre action valve hydraulic alarm bell, pressure switch, air compressor, air maintenance device, signal disc valve, etc., equipped with a closed sprinkler head, and commonly used detection systems as alarm and start devices.

其動(dòng)作原理:一旦發(fā)生火災(zāi),安裝在保護(hù)區(qū)感溫感煙火災(zāi)探測(cè)器發(fā)出火災(zāi)報(bào)等信號(hào),?;馂?zāi)報(bào)警控制器或消防控制中心,接到報(bào)警信號(hào)后發(fā)出指令打開雨淋閥上電磁閥,,使雨淋閥開啟,,壓力水流進(jìn)系統(tǒng)側(cè)管網(wǎng),變成濕式噴水系統(tǒng),,同時(shí)水力警鈴發(fā)出報(bào)苦,,壓力開關(guān)動(dòng)作反饋給控制中心顯示管路已充水,并啟動(dòng)消防泵,。
Its operating principle: In the event of a fire, a temperature and smoke sensing fire detector installed in the protected area will emit a fire alarm and other signals. After receiving the alarm signal, the fire alarm controller or fire control center sends a command to open the electromagnetic valve on the deluge valve, causing the deluge valve to open. The pressure water flows into the system side pipe network, becoming a wet water spraying system. At the same time, the hydraulic alarm bell emits a distress signal, and the pressure switch action feedback to the control center shows that the pipeline has been filled with water, and the fire pump is started.
此時(shí)管道上安裝閉式灑水噴頭尚未釋放,,不會(huì)噴水。人尚可主動(dòng)地經(jīng)主管人員采取適當(dāng)行動(dòng)將火撲滅,,避免噴頭動(dòng)作水漬造成的損失,。如果火災(zāi)控制不住繼續(xù)發(fā)展,致使閉式噴頭玻璃球動(dòng)作噴水,,水泵自動(dòng)啟動(dòng),。更多相關(guān)產(chǎn)品信息了解就來(lái)我們網(wǎng)站
http://n3462.cn咨詢!
At this point, the closed sprinkler head installed on the pipeline has not yet been released and will not spray water. People can actively take appropriate actions by the supervisory personnel to extinguish the fire and avoid losses caused by water stains caused by nozzle action. If the fire cannot be controlled and continues to develop, causing the closed nozzle glass ball to act and spray water, the water pump will automatically start. For more information on related products, come to our website http://n3462.cn consulting service