我們經(jīng)常會(huì)有患得患失的情況,對(duì)于廠房,,倉(cāng)庫(kù)來(lái)說(shuō),,需要保護(hù)廠房,倉(cāng)庫(kù)的產(chǎn)品和設(shè)備,,現(xiàn)階段使用
川消消防水炮是較為理想的消防防火,、滅火產(chǎn)品,但是在水炮調(diào)試的情況下會(huì)出現(xiàn)各種常見(jiàn)的問(wèn)題,。這種患得患失的情況下,,該怎么做呢?
We often have a situation of worrying about gains and losses. For factories and warehouses, it is necessary to protect the product and equipment safety of the factories and warehouses. Currently, using the Sichuan Fire Water Cannon is an ideal fire prevention and extinguishing product, but various common problems may arise during the debugging of the water cannon. What should we do in this situation of worrying about gains and losses?
01
01
有火源出現(xiàn),,水炮卻沒(méi)有反應(yīng)時(shí),,應(yīng)及時(shí)查看有沒(méi)有拆除火災(zāi)探測(cè)器(紅外,紫外)的保護(hù)罩,。
When a fire source appears but the water cannon does not respond, it is necessary to promptly check if the protective cover of the fire detector (infrared, ultraviolet) has been removed.
02
02
水炮能發(fā)現(xiàn)火源,,卻對(duì)不準(zhǔn)位置射水時(shí),應(yīng)分別對(duì)水炮的安裝高度,、垂直方向,、水平方向、定點(diǎn)時(shí)間等進(jìn)行系統(tǒng)參數(shù)調(diào)節(jié)
When the water cannon can detect the source of fire but shoots water from an inaccurate position, the system parameters such as the installation height, vertical direction, horizontal direction, and fixed point time of the water cannon should be adjusted separately
03
03
沒(méi)有火源出現(xiàn),水炮卻在自行啟動(dòng)時(shí),,要查看現(xiàn)場(chǎng)周圍是否有紅紫外干擾源,,應(yīng)對(duì)系統(tǒng)的紅紫外靈敏度進(jìn)行設(shè)置。
When there is no fire source present but the water cannon is starting on its own, it is necessary to check if there are any red and ultraviolet interference sources around the scene and set the red and ultraviolet sensitivity of the system.
04
04
水炮控制器開(kāi)機(jī)后,,卻發(fā)現(xiàn)“主電輸出”燈不亮?xí)r,,應(yīng)檢查機(jī)器內(nèi)為水炮供電的空氣開(kāi)關(guān)是否為開(kāi)啟狀態(tài),檢查鏈接空氣開(kāi)關(guān)的連接線是否有斷開(kāi),。
When the water cannon controller is turned on but the "main power output" light is not on, it is necessary to check whether the air switch supplying power to the water cannon in the machine is in an open state and whether the connecting wire to the air switch is disconnected.
05
05
水炮控制的液晶不顯示時(shí),,應(yīng)檢查液晶與顯示板是否連接完好,檢查背光插頭是否插好,。
When the LCD controlled by the water cannon does not display, it should be checked whether the LCD is properly connected to the display board and whether the backlight plug is plugged in properly.
06
06
水炮控制的鍵盤失效時(shí),,應(yīng)檢查軟面板插排是否完好,或可以重新查一下,。
When the keyboard of the water cannon control fails, it should be checked whether the soft panel plug is intact, or it can be rechecked.
07
07
水炮控制無(wú)音響出現(xiàn)時(shí),,應(yīng)檢查揚(yáng)聲器插頭是否插好,或可以重新插一下,。
When there is no sound in the water cannon control, it is necessary to check whether the speaker plug is properly plugged in, or it can be reinserted.
08
08
水炮控制器回路出現(xiàn)短路時(shí),,應(yīng)檢查回路總線,排查是否是短路,。
When there is a short circuit in the water cannon controller circuit, the circuit bus should be checked to see if it is a short circuit.
現(xiàn)在的智能化產(chǎn)品的智能程度比較高,,如果擔(dān)心設(shè)備穩(wěn)定性,那么可以對(duì)設(shè)備進(jìn)行多方面了解,,及時(shí)檢查設(shè)備,,消防水炮在國(guó)內(nèi)走過(guò)了很長(zhǎng)的低谷期,現(xiàn)在水炮性能已經(jīng)穩(wěn)定,,出錯(cuò)概率非常小,,反而作用越來(lái)越大。更多相關(guān)事項(xiàng)就來(lái)咨詢我們
http://n3462.cn吧,!
The current level of intelligence in intelligent products is relatively high. If you are concerned about the stability of the equipment, you can have a comprehensive understanding of the equipment and timely check the equipment. The fire water monitor has gone through a long period of decline in China, and now the performance of the water monitor is stable, with a very small probability of error, but the effect is becoming increasingly significant. Please consult us for more related matters http://n3462.cn Come on!