五月天手机无码av_色色图片区_97人人人人人人了_玖玖无码,免费无码片岛国在线看,A级毛片成年毛片20以上无码毛片,欧美成手机版在线视频,欧美一区高清,爱爱精品,成年轻人电影无码,h视频在线免费看

川消_萃聯(lián)
氣體滅火系統(tǒng)
自動(dòng)噴水滅火系統(tǒng)

聯(lián)系我們

  • 萃聯(lián)(山東)消防設(shè)備有限責(zé)任公司
  • 電話:15508683119
  • 地址:山東省濟(jì)南市歷城區(qū)祝舜路44號(hào)
當(dāng)前位置:首頁 > 新聞中心泡沫滅火系統(tǒng)的調(diào)試應(yīng)符合什么規(guī)定,?

泡沫滅火系統(tǒng)的調(diào)試應(yīng)符合什么規(guī)定,?

來源:http://n3462.cn/ 日期:2023-05-22

(1)當(dāng)為手動(dòng)滅火系統(tǒng)時(shí),應(yīng)以手動(dòng)控制的方式進(jìn)行一次噴水試驗(yàn),;當(dāng)為自動(dòng)滅火系統(tǒng)時(shí),,應(yīng)以手動(dòng)和自動(dòng)控制的方式各進(jìn)行一次噴水試驗(yàn),系統(tǒng)流量,、泡沫產(chǎn)生裝置的工作壓力,、比例混合裝置的工作壓力、系統(tǒng)的響應(yīng)時(shí)間均應(yīng)達(dá)到設(shè)計(jì)要求,。
(1) When using a manual fire extinguishing system, a water spray test should be conducted in a manually controlled manner; In case of an automatic fire extinguishing system, a water spray test shall be carried out manually and automatically. The system flow, the working pressure of the foam generating device, the working pressure of the proportioning device, and the response time of the system shall all meet the design requirements.
檢查數(shù)量:當(dāng)為手動(dòng)滅火系統(tǒng)時(shí),,選擇遠(yuǎn)的防護(hù)區(qū)或儲(chǔ)罐;當(dāng)為自動(dòng)滅火系統(tǒng)時(shí),,選擇所需泡沫混合液流量大和遠(yuǎn)的兩個(gè)防護(hù)區(qū)或儲(chǔ)罐分別以手動(dòng)和自動(dòng)的方式進(jìn)行試驗(yàn),。
Inspection quantity: When using a manual fire extinguishing system, select a remote protective area or storage tank; In case of automatic fire extinguishing system, two protection areas or storage tanks with large and far foam mixture flow shall be selected for test in manual and automatic ways respectively.
(2)川消小編提醒,低倍數(shù)泡沫滅火系統(tǒng)按本條第1款的規(guī)定噴水試驗(yàn)完畢,,將水放空后進(jìn)行噴泡沫試驗(yàn),;當(dāng)為自動(dòng)滅火系統(tǒng)時(shí),應(yīng)以自動(dòng)控制的方式進(jìn)行,;噴射泡沫的時(shí)間不宜小于1min,;實(shí)測泡沫混合液的流量、發(fā)泡倍數(shù)及到達(dá)遠(yuǎn)防護(hù)區(qū)或儲(chǔ)罐的時(shí)間應(yīng)符合設(shè)計(jì)要求,,混合比不應(yīng)低于所選泡沫液的混合比,。
(2) Sichuan Xiaobian reminds that the low expansion foam fire extinguishing system has completed the water spraying test according to the provisions of paragraph 1 of this article, and the foam spraying test is conducted after the water is emptied; When it is an automatic fire extinguishing system, it should be carried out in an automatic control manner; The time of spraying foam should not be less than 1min; The measured flow, foaming ratio and time to reach the far protection area or storage tank of foam mixture shall meet the design requirements, and the mixing ratio shall not be lower than that of the selected foam mixture.
川消
檢查數(shù)量:選擇遠(yuǎn)的防護(hù)區(qū)或儲(chǔ)罐,進(jìn)行一次試驗(yàn),。
Inspection quantity: Select a remote protective area or storage tank for one test.
(3)中倍數(shù),、高倍數(shù)泡沫滅火系統(tǒng)按本條第1款的規(guī)定噴水試驗(yàn)完畢,將水放空后進(jìn)行噴泡沫試驗(yàn),,當(dāng)為自動(dòng)滅火系統(tǒng)時(shí),,應(yīng)以自動(dòng)控制的方式對(duì)防護(hù)區(qū)進(jìn)行噴泡沫試驗(yàn),噴射泡沫的時(shí)間不宜小于30S,,實(shí)測泡沫供給速率及自接到火災(zāi)模擬信號(hào)開始噴泡沫的時(shí)間應(yīng)符合設(shè)計(jì)要求,,混合比不應(yīng)低于所選泡沫液的混合比。
(3) The medium and high expansion foam fire extinguishing systems shall be sprayed with foam after the completion of water spraying test according to the provisions of paragraph 1 of this article. In case of automatic fire extinguishing systems, foam spraying test shall be carried out in the protection area in an automatic control manner. The time of foam spraying shall not be less than 30s. The measured foam supply rate and the time from receiving the fire simulation signal to starting to spray foam shall meet the design requirements, The mixing ratio shall not be lower than that of the selected foam concentrate.
檢查數(shù)量:全數(shù)檢查,。
Inspection quantity: All inspections.
泡沫滅火系統(tǒng)的調(diào)試應(yīng)符合以上所講內(nèi)容規(guī)定,,希望對(duì)您有所幫助,,更多事項(xiàng)就來我們網(wǎng)站http://n3462.cn留言咨詢吧!
The commissioning of the foam fire extinguishing system should comply with the above provisions. I hope it will be helpful to you. For more information, please come to our website http://n3462.cn Leave a message for consultation!
上一篇:自動(dòng)跟蹤定位射流滅火系統(tǒng)應(yīng)符合這樣的要求,!
下一篇:川消自動(dòng)噴水滅火設(shè)備故障的5個(gè)常見原因

相關(guān)產(chǎn)品 / Related products