關(guān)于消防泵現(xiàn)場調(diào)試的一些知識和建議
來源:http://n3462.cn/ 日期:2023-05-24
消防泵場景的應(yīng)用非常常見,,廣泛應(yīng)用在各種工業(yè)領(lǐng)域,但在實際調(diào)試應(yīng)用的時候,,經(jīng)常遇到一些問題,,下面
川消小編向大家分享關(guān)于消防泵現(xiàn)場調(diào)試的一些知識和建議。
The application of the fire pump scene is very common and widely used in various industrial fields. However, some problems are often encountered in the actual commissioning application. Now, Chuanxiao Xiaobian will share some knowledge and suggestions about the on-site commissioning of fire pump.
水泵方面
In terms of water pumps
1.檢查水池水位,,是否高過水泵進水口(低位水池除外,,但需加裝底),。
1. Check whether the water level in the water tank is higher than the water inlet of the water pump (except for the low level water tank, which needs to be installed with a bottom).
2.檢查進水管路,,是否內(nèi)有異物(如焊渣類)拆開泵與管路連接處,放水沖洗,。
2. Check the water inlet pipeline for any foreign objects (such as welding slag). Remove the connection between the pump and the pipeline and discharge water for flushing.
3.打開水泵進出口門,,旋下水泵進出口法蘭上的排氣螺絲,排凈泵腔內(nèi)空氣,,水出為止,。
3. Open the inlet and outlet valves of the water pump, unscrew the exhaust screws on the inlet and outlet flanges of the water pump, and exhaust the air in the pump chamber until the water is discharged.
4.拆下水泵電機防護罩,用手扳動風(fēng)葉,,檢查水泵轉(zhuǎn)動是否靈活,。
4. Remove the protective cover of the water pump motor, pull the fan blades by hand, and check whether the water pump rotates flexibly.
5.檢查電源接線方面是否牢固,,是否。
5. Check if the power wiring is secure and safe.
控制柜方面
In terms of control cabinet
檢查控制柜外觀是否損壞,,內(nèi)部螺絲是否松動,。
Check whether the appearance of the control cabinet is damaged and whether the internal screws are loose.
按線路圖接好電源線,用儀表檢查是否缺相,,電壓是否正常,。
Connect the power cord according to the circuit diagram, and use an instrument to check for phase loss and normal voltage.
水泵暫時不接情況下,按手動啟動按鈕重復(fù)幾次,,看接觸器是否吸合正常,。
When the water pump is temporarily disconnected, press the manual start button several times to check if the contactor is working properly.
接上水泵電源線,點動(啟動后即停)看水泵轉(zhuǎn)向是否正常(正常為順時針旋轉(zhuǎn)),。
Connect the power cord of the water pump and jog (stop after starting) to check if the water pump rotates normally (clockwise rotation is normal).
如反轉(zhuǎn),,水泵電源線任意兩根線互調(diào)。
If reversed, any two lines of the water pump power line will be mutually adjustable.
按控制柜內(nèi)部門上的線路圖高,、中,、低位置,接電接點壓力表,??刂乒裾{(diào)為自動,測試壓力表,。如壓力表不會停止或啟動,,立即檢查信號線是否接反或其他。
Connect the electrical contact pressure gauge to the high, medium, and low positions on the internal door of the control cabinet according to the wiring diagram. Set the control cabinet to automatic and test the pressure gauge. If the pressure gauge does not stop or start, immediately check if the signal wire is connected in the wrong direction or otherwise.
注意事項
matters needing attention
·嚴(yán)禁水泵內(nèi)無水運轉(zhuǎn),,容易損壞機封,。
·It is strictly prohibited to operate the water pump without water, as it may damage the machine seal.
·嚴(yán)格按照控制柜內(nèi)線路圖接線,嚴(yán)禁改動控制路線,。
·Strictly follow the wiring diagram inside the control cabinet and strictly prohibit changing the control route.
·以上有未盡之處,,請人士規(guī)范操作。
·If there are any areas that are not covered above, please have professional personnel operate them in a standardized manner.
關(guān)于消防泵現(xiàn)場調(diào)試的一些知識和建議相關(guān)內(nèi)容就講解到這里了,,希望能夠給您好的幫助,,更多事項就來我們網(wǎng)站
http://n3462.cn咨詢!
This is the end of some knowledge and suggestions on the on-site commissioning of fire pump. I hope it can help you. More information can be found on our website http://n3462.cn consulting service