室外消火栓的設(shè)置要求有哪些?
來源:http://n3462.cn/ 日期:2023-09-11
市政消火栓
Municipal fire hydrant
(1)市政消火栓宜采用地上式室外消火栓;在嚴(yán)寒,、寒冷等冬季結(jié)冰地區(qū)宜采用干式地上式室外消火栓,,嚴(yán)寒地區(qū)宜增設(shè)消防水鶴。
(1) Municipal fire hydrants should use aboveground outdoor fire hydrants; Dry aboveground outdoor fire hydrants should be used in winter freezing areas such as severe cold, and fire water cranes should be added in severe cold areas.
當(dāng)采用地下式室外消火栓,,地下消火栓井的直徑不宜小于1.5m,,且當(dāng)?shù)叵率绞彝庀鹚ǖ娜∷谠诒鶅鼍€以上時(shí),應(yīng)采取保溫措施,。地下式市政消火栓應(yīng)有明顯的性標(biāo)志,。
When using underground outdoor fire hydrants, the diameter of the underground fire hydrant well should not be less than 1.5m, and when the water intake of the underground outdoor fire hydrant is above the freezing line, insulation measures should be taken. Underground municipal fire hydrants should have obvious permanent markings.
(2)市政消火栓宜采用直徑DN150的室外消火栓,并應(yīng)符合下列要求,。
(2) Municipal fire hydrants should use outdoor fire hydrants with a diameter of DN150 and meet the following requirements.
1)室外地上式消火栓應(yīng)有一個(gè)直徑為150mm或100mm和兩個(gè)直徑為65mm的栓口,。
1) Outdoor aboveground fire hydrants should have one diameter of 150mm or 100mm and two outlets with a diameter of 65mm.
2)室外地下式消火栓應(yīng)有直徑為100mm和65mm的栓口各一個(gè)。
2) Outdoor underground fire hydrants should have one hydrant mouth with a diameter of 100mm and one hydrant mouth with a diameter of 65mm.
(3)市政消火栓宜在道路的一側(cè)設(shè)置,,并宜靠近十字路口,,但當(dāng)市政道路寬度超過60.0m時(shí),應(yīng)在道路的兩側(cè)交叉錯(cuò)落設(shè)置市政消火栓,,市政橋橋頭和城市交通隧道出入口等市政公用設(shè)施處,,應(yīng)設(shè)置市政消火栓,其保護(hù)半徑不應(yīng)超過150m,,間距不應(yīng)大于120m,。
(3) Municipal fire hydrants should be installed on one side of the road and should be close to intersections. However, when the width of the municipal road exceeds 60.0m, municipal fire hydrants should be installed at intersections on both sides of the road. Municipal fire hydrants should be installed at municipal public facilities such as municipal bridge heads and urban traffic tunnel entrances and exits, with a protection radius of no more than 150m and a spacing of no more than 120m.
(4)市政消火栓應(yīng)布置在消防車易于接近的人行道和綠地等地點(diǎn),且不應(yīng)妨礙交通,。應(yīng)避免設(shè)置在機(jī)械易撞擊的地點(diǎn),,確有困難時(shí),應(yīng)采取防撞措施,。距路邊不宜小于0.5m,,并不應(yīng)大于2.0m,距建筑外墻或外墻邊緣不宜小于5.0m,。
(4) Municipal fire hydrants should be arranged in easily accessible pedestrian walkways and green spaces for fire trucks, and should not obstruct traffic. It should be avoided to set up in places where machinery is prone to collision. When it is indeed difficult, collision prevention measures should be taken. The distance from the roadside should not be less than 0.5m and should not be greater than 2.0m, and the distance from the exterior wall or edge of the building should not be less than 5.0m.
(5)當(dāng)市政給水管網(wǎng)設(shè)有市政消火栓時(shí),,其平時(shí)運(yùn)行工作壓力不應(yīng)小于0.14MPa,火災(zāi)時(shí)水力不利市政消火栓的出流量不應(yīng)小于15L/s,,且供水壓力從地面算起不應(yīng)小于0.10MPa,。
(5) When a municipal water supply network is equipped with a municipal fire hydrant, its normal operating pressure should not be less than 0.14MPa. In case of a fire, the flow rate of the municipal fire hydrant with unfavorable hydraulic conditions should not be less than 15L/s, and the water supply pressure should not be less than 0.10MPa from the ground.
2.室外消火栓
2. Outdoor fire hydrant
(2)建筑室外消火栓的數(shù)量應(yīng)根據(jù)室外消火栓設(shè)計(jì)流量和保護(hù)半徑經(jīng)計(jì)算確定,保護(hù)半徑不應(yīng)大于150.0m,,每個(gè)室外消火栓的出流量宜按10~15L/s計(jì)算,,室外消火栓宜沿建筑周圍均勻布置,,且不宜集中布置在建筑一側(cè);建筑消防撲救面一側(cè)的室外消火栓數(shù)量不宜少于2個(gè)。
(2) The number of outdoor fire hydrants in a building should be determined based on the design flow rate and protection radius of the outdoor fire hydrant. The protection radius should not exceed 150.0m, and the outlet flow rate of each outdoor fire hydrant should be calculated at 10-15L/s. Outdoor fire hydrants should be evenly arranged around the building and should not be concentrated on one side of the building; The number of outdoor fire hydrants on one side of the building's firefighting surface should not be less than 2.
(3)人防工程,、地下工程等建筑應(yīng)在出入口附近設(shè)置室外消火栓,,距出入口的距離不宜小于5m,并不宜大于40m;停車場(chǎng)的室外消火栓宜沿停車場(chǎng)周邊設(shè)置,,與一排汽車的距離不宜小于7m,,距加油站或油庫不宜小于15m。
(3) Buildings such as civil air defense engineering and underground engineering should have outdoor fire hydrants installed near the entrance and exit, with a distance of not less than 5m and not more than 40m from the entrance and exit; The outdoor fire hydrants in the parking lot should be set along the perimeter of the parking lot, with a distance of no less than 7m from a row of cars, and no less than 15m from a gas station or oil depot.
(4)甲,、乙,、丙類液體儲(chǔ)罐區(qū)和液化烴罐罐區(qū)等構(gòu)筑物的室外消火栓,應(yīng)設(shè)在防火堤或防護(hù)墻外,,數(shù)量應(yīng)根據(jù)每個(gè)罐的設(shè)計(jì)流量經(jīng)計(jì)算確定,,但距罐壁15m范圍內(nèi)的消火栓,不應(yīng)計(jì)算在該罐可使用的數(shù)量?jī)?nèi),。
(4) Outdoor fire hydrants for structures such as Class A, B, and C liquid storage tank areas and liquefied hydrocarbon tank areas should be installed outside the fire dike or protective wall. The quantity should be determined based on the design flow rate of each tank, but fire hydrants within 15m from the tank wall should not be included in the usable quantity of the tank.
(5)工藝裝置區(qū)等采用高壓或臨時(shí)高壓消防給水系統(tǒng)的場(chǎng)所,,其周圍應(yīng)設(shè)置室外消火栓,,數(shù)量應(yīng)根據(jù)設(shè)計(jì)流量經(jīng)計(jì)算確定,,且間距不應(yīng)大于60.0m。當(dāng)工藝裝置區(qū)寬度大于120.0m時(shí),,宜在該裝置區(qū)內(nèi)的路邊設(shè)置室外消火栓,。當(dāng)工藝裝置區(qū)、罐區(qū),、堆場(chǎng),、可燃?xì)怏w和液體碼頭等構(gòu)筑物的面積較大或高度較高,室外消火栓的充實(shí)水柱無法完全覆蓋時(shí),,宜在適當(dāng)部位設(shè)置室外固定消防炮,。
(5) Places such as process unit areas that use high-pressure or temporary high-pressure fire water supply systems should have outdoor fire hydrants installed around them. The quantity should be determined based on the design flow rate through calculation, and the spacing should not exceed 60.0m. When the width of the process unit area is greater than 120.0m, outdoor fire hydrants should be installed on the roadside within the unit area. When the area or height of structures such as process unit areas, tank farms, storage yards, flammable gas and liquid docks is large or high, and the full water column of outdoor fire hydrants cannot be fully covered, it is advisable to set up outdoor fixed fire monitors in appropriate locations.